A
Guide to Parallel Compressor System Oil ManagementOil management as applied to supermarket parallel compressor
rack systems is probably one of the least understood systems
BY STEVE ESSLINGER
Many service techs believe that an efficient oil
separator/management system will reduce the overall oil charge on a
properly operating refrigeration system. The fact is a refrigeration
system oil charge is greater with a highly efficient oil management
system as opposed to no oil management system.
This assertion is based on
the refrigeration system being properly installed, balanced and
maintained. Properly installed and maintained refrigeration systems
have adequate refrigerant velocities in the piping to return oil. To
offer an analogy, stand in drizzling rain for one hour and you’ll
get soaked. Stand in a downpour for five minutes and you’ll get
soaked. In either scenario, you are equally wet.
The total oil charge is equal to the
total of:
-
The oil in the field piping.
-
The oil in the compressor
crankcases.
-
The oil in the oil management
components.
With correct piping practices and
given a properly balanced refrigeration system, the oil charge in
the piping reaches a point where refrigerant velocities sweep excess
oil back to the compressors. This piping saturation point is the
same in a refrigeration system with or without an oil management
system.
Therefore, given equal time and a
system problem the difference is the amount of oil put into the
piping during the circuit run cycle. Less oil is logged in the
system with an efficient separator in a given time period as opposed
to a system with no separator when refrigerant velocities fall off.
It is important to note that an oil
management system works like a mechanical time delay to limit the
amount of oil movement into the piping between defrost cycles. When
defrost is terminated, the pressure/velocity is high enough to
return any excess oil that has been trapped in the system.
Oil is trapped in the piping when
common maintenance problems reduce heat transfer and reduce
refrigerant velocity. These include:
-
Thermostatic expansion valve (TEV)
with high superheat.
-
Honeycomb diffuser plugged with
dirt limiting air movement.
-
Stopped drains and ice impacted
evaporators.
-
Store humidity is higher than 55
percent, causing heavily frosted evaporators and minimal heat
transfer.
-
Evaporator fans are out.
According to one compressor
manufacturer, nine out of 10 compressor mechanical failures are
caused by oil slugs. Oil levels that rise significantly after
defrost termination are an indicator of system abnormalities. The
problem should be identified and corrected.
Understanding recirculation rates
Compressor oil recirculation rates
are 1 percent to 3 percent of the number of pounds of refrigerant
for which a compressor is rated. As an example, an average
100-horsepower, lowtemperature, R-404A parallel supermarket rack
system will have a minimum of 90 pounds of oil in recirculation an
hour at design conditions (1 percent oil recirculation). Note that
worn compressors can and do have much higher oil recirculation
rates.
Oil recirculation rates are
dependent on three things:
Maintaining correct compressor
crankcase oil levels on a parallel refrigeration rack with differing
size compressors (multiplexed) can be challenging at best. As an
example, a 15-horsepower compressor on a medium-temperature
application will have an oil recirculation rate of 18 pounds an hour
at 1 percent.
On the same rack a 5-horsepower
compressor that is more worn will have an oil recirculation rate of
5 percent and will discharge 25 pounds of oil an hour when running.
The smaller compressor has a higher oil recirculation rate compared
to the larger compressor. While unexpected, it is a real world oil
management problem.
With a common suction line it is
easy to see why some compressor crankcases are overfilled when the
float assemblies are working perfectly. Oil returns to the suction
header at an average rate of the combined operating compressors. The
return rate may exceed the discharge rate of one or more compressors
leading to compressor oil overfilling.
Oil-float assemblies are designed to
control low oil levels, not high oil levels. Additionally,
compressors that are on extended off cycles will overfill with oil.
This is because of the minimal but normal discharge vapor leakage
past the valves into the compressor. The vapor moves to suction and
the oil drops out into the compressor body through impingement.
Oil management systems have fallen
short in several areas:
-
High oil levels in compressor
crankcases occur when oil returning through the suction gas is
greater than the compressor discharge.
-
Oil slugs from the evaporator can
return directly into the compressor body causing mechanical
failure.
-
Oil slug builds up in the
compressor crankcase due to extended periods in the off cycle,
causing mechanical failure when compressor starts.
-
Do not offer external pumping to
continuously move and filter lubricant to eliminate the need for
changes (due to suspended particulate).
New technology addresses problems
One refrigeration company introduced
an oil management system in 2004 with a patent pending that
addresses these common problems. The cost is about the same as a
polyolester (POE) oil change on an average supermarket rack system.
The improved parallel compressor oil
management system:
-
Corrects high compressor oil
levels when oil in the suction gas exceeds the amount of oil
leaving in the discharge gas.
-
Traps oil slugs in the suction
header for removal before compressor damage occurs.
-
Continuously adjusts oil level to
3/8-inch of a sightglass in operating and non-operating
compressors.
-
Continuously pumps compressor
crankcase oil through filter, eliminating the need for oil changes
(due to suspended particulate).
Parts in the new system include
(numbers correspond to diagram above):
1.
Oil float. The oil level
float is designed with a special port to remove oil from the
compressor. This level is set at 3/8-inch of a sightglass as
recommended by most compressor vendors.
2.
Header drain tube. Suction
headers are designed with an elbow or "dip pocket" to collect excess
refrigerant and oil coming back to the suction side of the system.
The drain connection is connected to the suction side of the
maximizer pump.
3.
Check valve. Check valves are
used to prevent back flow into any compressor crankcase or suction
line if there are any compressor problems.
4.
Pump. Capable of pumping oil,
gas and liquid refrigerant.
5.
Oil filter. Special filter
removes 99 percent of 3 micron particulates from the oil.
6.
Differential check valve.
Differential check valve to vent high side pressure down to a
predetermined pressure over suction pressure to ensure oil flow to
compressor floats.
7.
Sightglass. Used to verify
oil flow in the system.
8.
Isolation valve. Used for
servicing components.
9.
Oil separator. Removes oil
from discharge gas.
10.
Oil reservoir. Used as a
storage vessel for oil.
11.
Solenoid valve (suction header).
The solenoid is closed under low superheat conditions to prevent
liquid refrigerant from being pumped to the oil reservoir.
Steve Esslinger
is vice president of operations at Zero Zone Refrigeration and a
member of the Manufacturers Service Advisory Council (MSAC).
|