The Meier Minute

www.MeierSupply.com

It only takes a minute to stay up-to-date with the Meier Minute

2007 Winter/Spring

 

In This Issue

·    ICM Head Pressure Controls

·    Superheat, Part 4 of 4

·    Lack of Flame Sense

Other Superheat articles

Visit our web site

Find lots of valuable information and other products we sell!

 

 

 

 

 

Contact Us

 

ICM Head Pressure Controls


ICM’s head pressure controls regulate system pressure to help prevent evaporator freeze-ups, low-pressure cutouts and liquid-slugged compressors in low ambient conditions that can lead to costly downtime and/or loss of valuable perishable goods. They can eliminate overshoots common to on/off pressure switch controls and also control refrigerant circuits. Features include hard start, low temperature cutoff and high temperature bypass. ICM's head pressure controls are ideal for air conditioning and refrigeration applications.

 

 

Meier Supply is your complete HVAC/R Wholesaler.

Call your local branch today!

 

Superheat

Part  4 of 4

As important as the superheat at the compressor inlet is, the temperature of the returning refrigerant is also very important. Most compressor manufacturers state that the return temperature should not exceed 65ºF.  With this in mind, if the saturated suction temperature leaving the evaporator was -40ºF and the return gas temperature was 65ºF, this is 105ºF of superheat.  Yes, this is too high of a superheat.  This high superheat would probably cause the compressor discharge temperature to also be too high.

 

The compressor must handle heat picked up in the refrigerant in circulation. The compressor cannot distinguish where the heat came from. The heat picked up in the suction line causes the overall system to be inefficient.  This will be the subject of another article.

 

George Story has been in the HVAC/R industry for 50 years. Most recently George was the Manager of Customer Training for the Copeland Corporation. In that position he was responsible for the renowned Compressor Operation and Service Seminar. Previously the manager of Meier Supply’s Erie store, he currently is Meier Supply’s Refrigeration, Air-Conditioning and Heating Technical Specialist.

 

 

TECHNICAL BULLETIN

February 2006

Lack of Flame Sense

The heating season is when we all begin to field some calls from our customers that are experiencing a problem with one of our Ruud furnaces.  One of the more  common problems that the technicians seem to encounter is a lack of flame sense.  When the furnace goes into a soft lockout the OK light on the IFC will have one blink.  Soft lockout is a result of four failed ignition attempts.  So what are some of the possible causes of failed ignition/flame sense?  First we must establish that the power supply is correctly polarized.  Have the tech test L1 to ground and he should read 120 volt.  Common to ground is 0 volt. 

Once it has been verified that the incoming power is correctly polarized we must establish that the furnace has been properly grounded.  A good ground is absolutely essential  for any furnace that utilizes a flame rectification system.  With flame rectification a small DC current is generated by the IFC through the burner flame via the flame rod.  That is why the burners must be properly grounded or the flame signal will not be detected.  The following is a quick and simple test procedure to determine a proper ground.

 

·         Set ohm meter to the lowest setting and then test from the burners to the common on the IFC.  The reading should be 0 ohms, however 1to 2 ohms is acceptable

·         Next test from the IFC common to ground and once again should read no more than 1 to 2 ohms resistance.

·         The last test is from the furnace ground to a cold water pipe and the reading must be no more than 1 to 2 ohms.

 

If  the resistance readings check out ok then pull apart the molex connectors in the furnace cabinet to ensure that they are dry and clean.  Moisture within the connectors may cause a flame sense failure.  Moisture will sometimes enter the furnace cabinet especially when a drain trap is not properly installed in the combustion air pipe.  This is a problem that will sometimes show up on a furnace that has been installed for awhile and suddenly begins to experience ignition failure.  Finally, the technician needs to make sure that the transformer is phased correctly.  Most technicians are familiar with making sure that the furnace is properly polarized, however many are not aware that the transformer needs to phased properly.  To check transformer phasing simply test between L1 of the primary and L1 of the secondary.  The voltage present should be a result of L1 primary minus L1 secondary.  Ideally you would read 96 volts.  If the voltage read is L1 primary plus L1 secondary (or 144 volts) then the technician would know that the transformer needs to phased and he would reverse the SECONDARY winding leads only.  In conclusion, flame sense failure can sometimes be a frustrating problem for all of us to figure out so hopefully I have given some tips that will be helpful in the future.  Please contact Steve Post at Meier Supply if you have any questions.